Envision Air Handler Installation Manual Page 18

  • Download
  • Add to my manuals
  • Print
  • Page
    / 24
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 17
18
ENVISION AIR HANDLER INSTALLATION MANUAL
Blower Performance
Blower Performance Variable Speed ECM
Model
Max
ESP
(wg)
Blower
Motor
(hp)
HP CFM Setting Normal Mode Htg & Clg Dehumidification Mode Clg Aux CFM Setting Aux
Emerg
Mode
S1 S2 Stg 2 Stg 1 Blower S9 Stg 2 Stg 1 Blower S5 S6
022
0.50 1/2 On On 900 700 450 Off 775 600 450 On On 1000
0.50 1/2
Off On 800 625 400
Off 680 530 400
Off On 800
0.50 1/2 On Off 700 540 375 Off 600 450 375 On Off 775
0.50 1/2 Off Off 640 480 350 Off Off 740
026
0.50 1/2 On On 1050 800 525 Off 850 700 525 On On 1150
0.50 1/2
Off On 925 725 475
Off 760 620 475
Off On 950
0.50 1/2 On Off 800 625 425 Off 670 540 425 On Off 925
0.50 1/2 Off Off 740 575 400 Off Off 825
030
0.50 1/2 On On 1150 950 600 Off 975 775 600 On On 1250
0.50 1/2
Off On 980 780 500
Off 825 640 500
Off On 1000
0.50 1/2 On Off 900 700 440 Off 750 580 440 On Off 975
0.50 1/2 Off Off 800 630 425 Off Off 900
036
0.50 1/2 On On 1300 1025 760 Off 1105 871 760 On On 1300
0.50 1/2
Off On 1225 950 685
Off 1041 808 685
Off On 1250
0.50 1/2 On Off 1150 850 620 Off 940 690 620 On Off 1225
0.50 1/2 Off Off 1075 800 550 Off Off 1200
042
0.75 1 On On 1500 1100 750 Off 1250 900 750 On On 1550
0.75 1
Off On 1425 1010 650
Off 1180 840 650
Off On 1450
0.75 1 On Off 1300 975 635 Off 1080 800 635 On Off 1400
0.75 1 Off Off 1150 850 625 Off Off 1275
048
0.75 1 On On 1700 1300 975 Off 1400 1080 975 On On 1700
0.75 1
Off On 1625 1240 875
Off 1350 1025 875
Off On 1550
0.75 1 On Off 1450 1100 750 Off 1200 900 750 On Off 1525
0.75 1 Off Off 1300 1000 675 Off Off 1400
060
0.75 1 On On 1850 1750 1175 Off 1540 1450 1175 On On 1850
0.75 1
Off On 1760 1625 1050
Off 1460 1350 1050
Off On 1760
0.75 1 On Off 1720 1575 1015 Off 1425 1300 1015 On Off 1725
0.75 1 Off Off 1680 1525 975 1428 Off Off 1700
2/3/10
Factory CFM settings are in boldface
CFM is controlled within 5% up to maximum ESP
Maximum ESP includes allowance for wet coil and standard fi lter
DIP switch 9 must be 'OFF' to select dehumidi cation mode
1
2
3
4
5
6
7
8
9
10
SW1
OnOff
Heating and Cooling
Auxiliary Heating
Dehumidification